HMM058
Description

Commercial Split Units

Electronic control panel
Expansion by means of thermal expansion valve
Cable for door heater (on low temperature units)
Fixed calibration low pressure switch
High pressure switch on all three-phase units and on single-phase HMM122-152
(in compliance with the “pressure equipment” directive 97/23/CE)
Direct drainage of condensate water with heater
Hermetic compressor
Electric defrost
Filter on the liquid line
Remote control panel connected to the unit with a 5m long cable
Sight glass
All units are equiped with a liquid receiver complying (in compliance with the
“pressure equipment” directive 97/23/CE)
Pre-arrangement for door switch and room light connections

HMM058

Technical data
Application NT
Coolant R452A
Expansion management Exp. Valve
Brand SICAF
Compressor type E
Displacement 2,49 cc
Power absorption (W) 920
Tension 230/1/50
 
Condenser fan 1X254 mm
Condenser air flow 1050 mc/h
Evaporator fans 1X254 mm
Evaporator air flow 810 mc/h
Air throw m.6
 
Package W x D x H (C) 850x690x640 mm
Gross weight 62 Kg
Package W x D x H (E) 710x620x390 mm
Gross weight 20 Kg
 
Cooling capacity
Cold room temperature →
↓ Ambient temperature
+5°C 0°C -5°C
+20°C W
m3
1504
15,5
1315
12,8
1147
9,8
+32°C W
m3
1275
12,8
1119
9,5
933
6,9
+43°C W
m3
1096
8,7
928
6,8
777
5