HMM100

Description
Commercial Split Units
Electronic control panel
Expansion by means of thermal expansion valve
Cable for door heater (on low temperature units)
Fixed calibration low pressure switch
High pressure switch on all three-phase units and on single-phase HMM122-152
(in compliance with the “pressure equipment” directive 97/23/CE)
Direct drainage of condensate water with heater
Hermetic compressor
Electric defrost
Filter on the liquid line
Remote control panel connected to the unit with a 5m long cable
Sight glass
All units are equiped with a liquid receiver complying (in compliance with the
“pressure equipment” directive 97/23/CE)
Pre-arrangement for door switch and room light connections
HMM100
Technical data
Application
NT
Coolant
R452A
Expansion management
Exp. Valve
Brand
SICAF
Compressor type
E
Displacement
3,89 cc
Power absorption (W)
1470
Tension
230/1/50
Condenser fan
1X300 mm
Condenser air flow
1610 mc/h
Evaporator fans
2X254 mm
Evaporator air flow
1590 mc/h
Air throw
m.6
Package W x D x H (C)
850x690x640 mm
Gross weight 70 Kg
Package W x D x H (E)
1010x620x390 mm
Gross weight
28 Kg
Cooling capacity
Cold room temperature → ↓ Ambient temperature |
+5°C | 0°C | -5°C | |
---|---|---|---|---|
+20°C |
W m3 |
2510 30,1 |
2182 22,9 |
1867 17,7 |
+32°C |
W m3 |
2057 24,1 |
1797 18,9 |
1475 13,6 |
+43°C |
W m3 |
1747 17,6 |
1459 13,3 |
1225 10,4 |