Skip to main content

ACL230

Generate PDF

ACL230
Description

Straddle mounting as standard, optional
panel through the wall installation

Electronic control instrument
Expansion device: capillary tube
Cable for door heater (on all low temperature units)
Cable for cold room lighting
Fixed calibration low pressure switch
High pressure switch on all three-phase
units and on single-phase models
ACM122-152 (this outfit complies with the
provisions of the “pressure equipment directive
97/23/CE)
Condensate evaporation tray with safety overflow drain
Drain heater
Hermetic compressor
Hot gas defrost
Filter on the liquid line
Prearrangement for door micro switch connection

Documenti generali

ACL230

Technical data
Application LT
Coolant R452A
Expansion management Exp. Capillary
Brand SICAF
Compressor type E
Displacement 11,54 cc
Power absorption (W) 2630
Tension 400/3/50
 
Condenser fan 2X254 mm
Condenser air flow 2100 mc/h
Evaporator fans 2X200 mm
Evaporator air flow 1100 mc/h
Air throw m.5
 
Package W x D x H 900x830x920 mm
Gross weight 96 Kg
 
Cooling capacity
Cold room temperature →
↓ Ambient temperature
-18°C -22°C -25°C
+20°C W
m3
2610
35
2145
26,6
1810
20,7
+32°C W
m3
1960
21,1
1565
15,4
1335
12,1
+43°C W
m3
1475
15,7
1185
11,3
1005
8,7